OPC UA Historical Access (HA)
Available from 2019.6
Standard OPC UA® HA enables the OPC UA® clients to access the historical data of the PLCnext Technology DataLogger. You can call selected variables from a database using OPC UA® HA. To use OPC UA® HA for the data of GDS variables, the variables must be present in at least one DataLogger session (available for data sink types db
and volatile
). For further information on the DataLogger, please refer to the DataLogger section.
Note: Only scalars and strings are supported. If a variable is present in more than one DataLogger session, the session with the smallest sampling interval will automatically be used.
OPC UA server capabilities
The OPC UA® server capabilities provide the OPC UA® client with information on the server properties and possibilities. The OPC UA® client can access the server capabilities in the information model of the OPC UA® server. The HA-specific OPC UA® server capabilities (HistoryServerCapabilities
) provide information on access to the historical data. The AccessHistoryDataCapability
node is TRUE
. Any other nodes are FALSE
. Additional information is available for the OPC UA® client via a ServerCapabilityIdentifier
. The HD (Historical Data) entry informs the OPC UA® client about historical data being provided.
OPC UA AccessLevel
For GDS variables that are present in a DataLogger session, the HistoryRead bit in the AccessLevel or UserAccessLevel OPC UA® attribute is TRUE. In this way, the historical data is available and can be read via the OPC UA® server.
Retrieving historical data
The OPC UA® server implements the ReadRaw
function in accordance with OPC UA® Specification 1.03 Part 11. The ReadRawModified
service can be used to retrieve the historical data. Section 6.4.3 of the specification describes the service. The ReadModified
function is not supported, as only raw data can be read. The isReadModified
parameter must therefore be FALSE
.
The following parameters of the ReadRawModified
are supported in accordance with the OPC UA® specification:
Parameter | Description |
ReadRawModifiedDetails |
Specifies the request of historical data |
startTime |
Start time for the period of data retrieval |
endTime |
End time for the period of data retrieval |
numValuesPerNode |
Maximum number of values that is to be returned for each node within the period. Value 0 = No maximum value specified |
returnBounds |
TRUE = Limit values are to be returnedFALSE = Any other cases
|
Further information, application examples, and error codes can be found in the OPC UA® specification.
Tutorial video
Note: Tutorial videos are embedded from the Phoenix Contact Technical Support YouTube channel. With playing an embedded YouTube video in this platform, you accept the YouTube Terms & Conditions.
Even showing the video previews on this page depends on your personal settings in the Cookie consent dialog. To watch YouTube videos, you have to allow cookies for marketing purposes which will remain on your device. The data gained through these cookies will be used by YouTube to provide video suggestions and advertisements based on your browsing habits, and may be made available to other parties.